General information | | | | | | |
Product type designation | CPU 1212FC DC/DC/DC | CPU 1212FC DC/DC/relay | CPU 1214FC DC/DC/DC | CPU 1214FC DC/DC/Relay | CPU 1215FC DC/DC/DC | CPU 1215FC DC/DC/relay |
Firmware version | V4.5 | V4.5 | V4.5 | V4.5 | V4.5 | V4.5 |
Engineering with | | | | | | |
| STEP 7 V17 or higher | STEP 7 V17 or higher | STEP 7 V17 or higher | STEP 7 V17 or higher | STEP 7 V17 or higher | STEP 7 V17 or higher |
Supply voltage | | | | | | |
Rated value (DC) | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
permissible range, lower limit (DC) | 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V |
permissible range, upper limit (DC) | 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V |
Reverse polarity protection | Yes | | Yes | | Yes | Yes |
Load voltage L+ | | | | | | |
| 24 V | 24 V | 24 V | 24 V | 24 V | 24 V |
| 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V | 20.4 V |
| 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V | 28.8 V |
Input current | | | | | | |
Current consumption (rated value) | 400 mA; CPU only | 400 mA; CPU only | 500 mA; CPU only | 500 mA; CPU only | 500 mA; CPU only | 500 mA; CPU only |
Current consumption, max. | 1 200 mA; CPU with all expansion modules | 1 200 mA; CPU with all expansion modules | 1 500 mA; CPU with all expansion modules | 1 500 mA; CPU with all expansion modules | 1 500 mA; CPU with all expansion modules | 1 500 mA; CPU with all expansion modules |
Inrush current, max. | 12 A; at 28.8 V DC | 12 A; at 28.8 V | 12 A; at 28.8 V | 12 A; at 28.8 V | 12 A; at 28.8 V DC | 12 A; at 28.8 V DC |
I²t | 0.5 A²·s | 0.8 A²·s | 0.5 A²·s | 0.8 A²·s | 0.5 A²·s | 0.5 A²·s |
Output current | | | | | | |
for backplane bus (5 V DC), max. | 1 000 mA; Max. 5 V DC for SM and CM | 1 000 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM | 1 600 mA; Max. 5 V DC for SM and CM |
Encoder supply | | | | | | |
24 V encoder supply | | | | | | |
| L+ minus 4 V DC min. | L+ minus 4 V DC min. | L+ minus 4 V DC min. | L+ minus 4 V DC min. | L+ minus 4 V DC min. | L+ minus 4 V DC min. |
Power loss | | | | | | |
Power loss, typ. | 9 W | 9 W | 12 W | 12 W | 12 W | 12 W |
Memory | | | | | | |
Work memory | | | | | | |
| 100 kbyte | 100 kbyte | 125 kbyte | 125 kbyte | 150 kbyte | 150 kbyte |
Load memory | | | | | | |
| 2 Mbyte | 2 Mbyte | 4 Mbyte | 4 Mbyte | 4 Mbyte | 4 Mbyte |
| with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card | with SIMATIC memory card |
Backup | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
CPU processing times | | | | | | |
for bit operations, typ. | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction | 0.08 µs; / instruction |
for word operations, typ. | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction | 1.7 µs; / instruction |
for floating point arithmetic, typ. | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction | 2.3 µs; / instruction |
CPU-blocks | | | | | | |
Number of blocks (total) | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used | DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used |
OB | | | | | | |
| Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code | Limited only by RAM for code |
Data areas and their retentivity | | | | | | |
Retentive data area (incl. timers, counters, flags), max. | 14 kbyte | 14 kbyte | 14 kbyte | 14 kbyte | 14 kbyte | 14 kbyte |
Flag | | | | | | |
| 4 kbyte; Size of bit memory address area | 4 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area | 8 kbyte; Size of bit memory address area |
Local data | | | | | | |
| 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB | 16 kbyte; Priority class 1 (program cycle): 16 KB, priority class 2 to 26: 6 KB |
Address area | | | | | | |
Process image | | | | | | |
| 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte |
| 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte | 1 kbyte |
Hardware configuration | | | | | | |
Number of modules per system, max. | 3 comm. modules, 1 signal board, 2 signal modules | 3 comm. modules, 1 signal board, 2 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | 3 comm. modules, 1 signal board, 8 signal modules | 3 comm. modules, 1 signal board, 8 signal modules |
Time of day | | | | | | |
Clock | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 480 h; Typical | 480 h; Typical | 480 h; Typical | 480 h; Typical | 480 h; Typical | 480 h; Typical |
| 60 s/month at 25 °C | ±60 s/month at 25 °C | ±60 s/month at 25 °C | ±60 s/month at 25 °C | ±60 s/month at 25 °C | ±60 s/month at 25 °C |
Digital inputs | | | | | | |
Number of digital inputs | 8; Integrated | 8; Integrated | 14; Integrated | 14; Integrated | 14; Integrated | 14; Integrated |
| 4; HSC (High Speed Counting) | 4; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) | 6; HSC (High Speed Counting) |
Source/sink input | Yes | Yes | Yes | Yes | Yes | Yes |
Number of simultaneously controllable inputs | | | | | | |
all mounting positions | | | | | | |
| 8 | 8 | 14 | 14 | 14 | 14 |
Input voltage | | | | | | |
| 24 V | 24 V | 24 V | 24 V | 24 V | 24 V |
| 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA | 5 V DC at 1 mA |
| 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA | 15 V DC at 2.5 mA |
Input delay (for rated value of input voltage) | | | | | | |
for standard inputs | | | | | | |
| 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four | Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four |
| 0.2 ms | 0.2 ms | 0.2 ms | 0.2 ms | 0.2 ms | 0.2 ms |
| 12.8 ms | 12.8 ms | 12.8 ms | 12.8 ms | 12.8 ms | 12.8 ms |
for interrupt inputs | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
for technological functions | | | | | | |
| Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz | Single phase: 3 @ 100 kHz & 3 @ 30 kHz, differential: 3 @ 80 kHz & 3 @ 30 kHz |
Cable length | | | | | | |
| 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions | 500 m; 50 m for technological functions |
| 300 m; for technological functions: No | 300 m; for technological functions: No | 300 m; for technological functions: No | 300 m; for technological functions: No | 300 m; for technological functions: No | 300 m; for technological functions: No |
Digital outputs | | | | | | |
Number of digital outputs | 6 | 6; Relays | 10 | 10; Relays | 10 | 10; Relays |
| 4; 100 kHz Pulse Train Output | | 4; 100 kHz Pulse Train Output | | 4; 100 kHz Pulse Train Output | |
Limitation of inductive shutdown voltage to | L+ (-48 V) | | L+ (-48 V) | | L+ (-48 V) | |
Switching capacity of the outputs | | | | | | |
| 0.5 A | 2 A | 0.5 A | 2 A | 0.5 A | 2 A |
| 5 W | 30 W with DC, 200 W with AC | 5 W | 30 W with DC, 200 W with AC | 5 W | 30 W with DC, 200 W with AC |
Output voltage | | | | | | |
| 0.1 V; with 10 kOhm load | | 0.1 V; with 10 kOhm load | | 0.1 V; with 10 kOhm load | |
| 20 V | | 20 V | | 20 V | |
Output current | | | | | | |
| 0.5 A | | 0.5 A | | 0.5 A | |
| 0.1 mA | | 0.1 mA | | 0.1 mA | |
Output delay with resistive load | | | | | | |
| 1 µs | 10 ms; max. | 1 µs | 10 ms; max. | 1 µs | 10 ms; max. |
| 5 µs | 10 ms; max. | 5 µs | 10 ms; max. | 5 µs | 10 ms; max. |
Switching frequency | | | | | | |
| 100 kHz | | 100 kHz | | 100 kHz | |
Relay outputs | | | | | | |
| 0 | 6 | 0 | 10 | 0 | 10 |
| | mechanically 10 million, at rated load voltage 100 000 | | mechanically 10 million, at rated load voltage 100 000 | | mechanically 10 million, at rated load voltage 100 000 |
Cable length | | | | | | |
| 500 m | 500 m | 500 m | 500 m | 500 m | 500 m |
| 150 m | 150 m | 150 m | 150 m | 150 m | 150 m |
Analog inputs | | | | | | |
Number of analog inputs | 2 | 2 | 2 | 2 | 2 | 2 |
Input ranges | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
Input ranges (rated values), voltages | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| ≥100k ohms | ≥100k ohms | ≥100k ohms | ≥100k ohms | ≥100k ohms | ≥100k ohms |
Cable length | | | | | | |
| 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded | 100 m; twisted and shielded |
Analog outputs | | | | | | |
Number of analog outputs | 0 | 0 | 0 | 0 | 2 | 2 |
Output ranges, current | | | | | | |
| | | | | Yes | Yes |
Analog value generation for the inputs | | | | | | |
Integration and conversion time/resolution per channel | | | | | | |
| 10 bit | 10 bit | 10 bit | 10 bit | 10 bit | 10 bit |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 625 µs | 625 µs | 625 µs | 625 µs | 625 µs | 625 µs |
Analog value generation for the outputs | | | | | | |
Integration and conversion time/resolution per channel | | | | | | |
| | | | | 10 bit | 10 bit |
Encoder | | | | | | |
Connectable encoders | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
1. Interface | | | | | | |
Interface type | PROFINET | PROFINET | PROFINET | PROFINET | PROFINET | PROFINET |
Isolated | Yes | Yes | Yes | Yes | Yes | Yes |
automatic detection of transmission rate | Yes | Yes | Yes | Yes | Yes | Yes |
Autonegotiation | Yes | Yes | Yes | Yes | Yes | Yes |
Autocrossing | Yes | Yes | Yes | Yes | Yes | Yes |
Interface types | | | | | | |
| Yes | | Yes | Yes | Yes | Yes |
| 1 | 1 | 1 | 1 | 2 | 2 |
| No | No | No | No | Yes | Yes |
Protocols | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes; Optionally also encrypted | Yes; Optionally also encrypted | Yes; Optionally also encrypted | Yes; Optionally also encrypted | Yes; Optionally also encrypted | Yes; Optionally also encrypted |
| Yes | Yes | Yes | Yes | Yes | Yes |
| No | No | No | No | Yes; as MRP client | Yes |
PROFINET IO Controller | | | | | | |
| 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s | 100 Mbit/s |
Services | | | | | | |
| Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected |
| No | No | No | No | No | No |
| No | No | No | No | No | No |
| No | No | No | No | No | No |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 16 | 16 | 16 | 16 | 16 | 16 |
| 16 | 16 | 16 | 16 | 16 | 16 |
| 16 | 16 | 16 | 16 | 16 | 16 |
| 16 | 16 | 16 | 16 | 16 | 16 |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 8 | 8 | 8 | 8 | 8 | 8 |
| The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. | The minimum value of the update time also depends on the communication component set for PROFINET IO, on the number of IO devices and the quantity of configured user data. |
PROFINET IO Device | | | | | | |
Services | | | | | | |
| Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected | Yes; encryption with TLS V1.3 pre-selected |
| No | No | No | No | No | No |
| No | No | No | No | No | No |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 2 | 2 | 2 | 2 | 2 | 2 |
Protocols | | | | | | |
Supports protocol for PROFINET IO | Yes | Yes | Yes | Yes | Yes | Yes |
PROFIsafe | Yes | Yes | Yes | Yes | Yes | Yes |
PROFIBUS | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required | Yes; CM 1243-5 (master) or CM 1242-5 (slave) required |
OPC UA | Yes; OPC UA Server | Yes; OPC UA Server | Yes; OPC UA Server | Yes; OPC UA Server | Yes; OPC UA Server | Yes; OPC UA Server |
AS-Interface | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required | Yes; CM 1243-2 required |
Protocols (Ethernet) | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| No | No | No | No | No | No |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
Redundancy mode | | | | | | |
Media redundancy | | | | | | |
| No | No | | | Yes; as MRP redundancy manager and/or MRP client | Yes; as MRP redundancy manager and/or MRP client |
| No | No | | | No | No |
SIMATIC communication | | | | | | |
| | | | | Yes | Yes |
Open IE communication | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte | 8 kbyte |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 1 472 byte | 1 472 byte | 1 472 byte | 1 472 byte | 1 472 byte | 1 472 byte |
Web server | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
OPC UA | | | | | | |
| Yes; "Basic" license required | Yes; "Basic" license required | Yes; "Basic" license required | Yes; "Basic" license required | Yes; "Basic" license required | Yes; "Basic" license required |
| Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required | Yes; data access (read, write, subscribe), method call, runtime license required |
| Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 | Available security policies: None, Basic128Rsa15, Basic256Rsa15, Basic256Sha256 |
| "anonymous" or by user name & password | "anonymous" or by user name & password | "anonymous" or by user name & password | "anonymous" or by user name & password | "anonymous" or by user name & password | "anonymous" or by user name & password |
| 10 | 10 | 10 | 10 | 10 | 10 |
| 5 | 5 | 5 | 5 | 5 | 5 |
| 100 ms | 100 ms | 100 ms | 100 ms | 100 ms | 100 ms |
| 200 ms | 200 ms | 200 ms | 200 ms | 200 ms | 200 ms |
| 20 | 20 | 20 | 20 | 20 | 20 |
| 1 000 | 1 000 | 1 000 | 1 000 | 1 000 | 1 000 |
| 2 | 2 | 2 | 2 | 2 | 2 |
| 2 000 | 2 000 | 2 000 | 2 000 | 2 000 | 2 000 |
Further protocols | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
communication functions / header | | | | | | |
S7 communication | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) | See online help (S7 communication, user data size) |
Number of connections | | | | | | |
| PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max | PG Connections: 4 reserved / 4 max; HMI Connections: 12 reserved / 18 max; S7 Connections: 8 reserved / 14 max; Open User Connections: 8 reserved / 14 max; Web Connections: 2 reserved / 30 max; OPC UA Connections: 0 reserved / 10 max; Total Connections: 34 reserved / 64 max |
Test commissioning functions | | | | | | |
Status/control | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters | inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters | inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters | inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters | inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters | inputs/outputs, bit memories, DBs, peripheral I/Os (without fail-safe), times, counters |
Forcing | | | | | | |
| Yes; peripheral inputs/outputs (without fail-safe) | Yes; peripheral inputs/outputs (without fail-safe) | Yes; peripheral inputs/outputs (without fail-safe) | Yes; peripheral inputs/outputs (without fail-safe) | Yes; peripheral inputs/outputs (without fail-safe) | Yes; peripheral inputs/outputs (without fail-safe) |
Diagnostic buffer | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
Traces | | | | | | |
| 2 | 2 | 2 | 2 | 2 | 2 |
| 512 kbyte | 512 kbyte | 512 kbyte | 512 kbyte | 512 kbyte | 512 kbyte |
Interrupts/diagnostics/status information | | | | | | |
Diagnostics indication LED | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
Integrated Functions | | | | | | |
Frequency measurement | Yes | Yes | Yes | Yes | Yes | Yes |
controlled positioning | Yes | Yes | Yes | Yes | Yes | Yes |
Number of position-controlled positioning axes, max. | 8 | 8 | 8 | 8 | 8 | 8 |
Number of positioning axes via pulse-direction interface | Up to 4 with SB 1222 | Up to 4 with SB 1222 | 4; With integrated outputs | Up to 4 with SB 1222 | 4; With integrated outputs | Up to 4 with SB 1222 |
PID controller | Yes | Yes | Yes | Yes | Yes | Yes |
Number of alarm inputs | 4 | 4 | 4 | 4 | 4 | 4 |
Number of pulse outputs | 4 | | 4 | | 4 | |
Limit frequency (pulse) | 100 kHz | | 100 kHz | | 100 kHz | |
Potential separation | | | | | | |
Potential separation digital inputs | | | | | | |
| No | 500V AC for 1 minute | No | 500V AC for 1 minute | No | 500V AC for 1 minute |
| 1 | 1 | 1 | 1 | 1 | 1 |
Potential separation digital outputs | | | | | | |
| Yes | Relays | Yes | Relays | Yes | Relays |
| No | No | No | No | No | No |
| 1 | 2 | 1 | 2 | 1 | 2 |
EMC | | | | | | |
Interference immunity against discharge of static electricity | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| 8 kV | 8 kV | 8 kV | 8 kV | 8 kV | 8 kV |
| 6 kV | 6 kV | 6 kV | 6 kV | 6 kV | 6 kV |
Interference immunity to cable-borne interference | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
Interference immunity against voltage surge | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
Interference immunity against conducted variable disturbance induced by high-frequency fields | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
Emission of radio interference acc. to EN 55 011 | | | | | | |
| Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 | Yes; Group 1 |
| Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 | Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011 |
Degree and class of protection | | | | | | |
IP degree of protection | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 |
Standards, approvals, certificates | | | | | | |
CE mark | Yes | Yes | Yes | Yes | Yes | Yes |
UL approval | Yes | Yes | Yes | Yes | Yes | Yes |
cULus | Yes | Yes | Yes | Yes | Yes | Yes |
FM approval | Yes | Yes | Yes | Yes | Yes | Yes |
RCM (formerly C-TICK) | Yes | Yes | Yes | Yes | Yes | Yes |
KC approval | Yes | Yes | Yes | Yes | Yes | Yes |
Marine approval | Yes | Yes | Yes | Yes | Yes | Yes |
Highest safety class achievable in safety mode | | | | | | |
| PLe | PLe | PLe | PLe | PLe | PLe |
| SIL 3 | SIL 3 | SIL 3 | SIL 3 | SIL 3 | SIL 3 |
Ambient conditions | | | | | | |
Free fall | | | | | | |
| 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package | 0.3 m; five times, in product package |
Ambient temperature during operation | | | | | | |
| 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | 0 °C |
| 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical | 55 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical |
| 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | 0 °C |
| 55 °C | 55 °C | 55 °C | 55 °C | 55 °C | 55 °C |
| 0 °C | 0 °C | 0 °C | 0 °C | 0 °C | 0 °C |
| 45 °C | 45 °C | 45 °C | 45 °C | 45 °C | 45 °C |
Ambient temperature during storage/transportation | | | | | | |
| -40 °C | -40 °C | -40 °C | -40 °C | -40 °C | -40 °C |
| 70 °C | 70 °C | 70 °C | 70 °C | 70 °C | 70 °C |
Air pressure acc. to IEC 60068-2-13 | | | | | | |
| 795 hPa | 795 hPa | 795 hPa | 795 hPa | 795 hPa | 795 hPa |
| 1 080 hPa | 1 080 hPa | 1 080 hPa | 1 080 hPa | 1 080 hPa | 1 080 hPa |
| 660 hPa | 660 hPa | 660 hPa | 660 hPa | 660 hPa | 660 hPa |
| 1 080 hPa | 1 080 hPa | 1 080 hPa | 1 080 hPa | 1 080 hPa | 1 080 hPa |
Altitude during operation relating to sea level | | | | | | |
| -1 000 m | -1 000 m | -1 000 m | -1 000 m | -1 000 m | -1 000 m |
| 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual | 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual |
Relative humidity | | | | | | |
| 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation | 95 %; no condensation |
Vibrations | | | | | | |
| 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail | 2 g (m/s²) wall mounting, 1 g (m/s²) DIN rail |
| Yes | Yes | Yes | Yes | Yes | Yes |
Shock testing | | | | | | |
| Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms | Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms |
Pollutant concentrations | | | | | | |
| S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free | S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free |
configuration / header | | | | | | |
configuration / programming / header | | | | | | |
Programming language | | | | | | |
| Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe |
| Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe | Yes; incl. failsafe |
| Yes | Yes | Yes | Yes | Yes | Yes |
Know-how protection | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
Access protection | | | | | | |
| Yes | | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
| Yes | Yes | Yes | Yes | Yes | Yes |
programming / cycle time monitoring / header | | | | | | |
| Yes | Yes | Yes | Yes | Yes | Yes |
Dimensions | | | | | | |
Width | 90 mm | 90 mm | 110 mm | 110 mm | 130 mm | 130 mm |
Height | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm | 100 mm |
Depth | 75 mm | 75 mm | 75 mm | 75 mm | 75 mm | 75 mm |
Weights | | | | | | |
Weight, approx. | 370 g | 385 g | 415 g | 435 g | 500 g | 585 g |